SecurityContext

CVE-2018-13814: Siemens SIMATIC HMI - HTTP Header Injection

  • Cve: CVE-2018-13814
  • Name: Siemens SIMATIC HMI - HTTP Header Injection
  • Description: A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V14), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V14), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V14), SIMATIC WinCC Runtime Advanced (All versions < V14), SIMATIC WinCC Runtime Professional (All versions < V14), SIMATIC WinCC (TIA Portal) (All versions < V14), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The integrated web server (port 80/tcp and port 443/tcp) of the affected devices could allow an attacker to inject HTTP headers. An attacker must trick a valid user who is authenticated to the device into clicking on a malicious link to exploit the vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
  • Impact: Attackers can inject malicious HTTP headers, potentially leading to session hijacking or other web-based attacks.
  • Remediation: Update to version V14 or later of affected devices.
  • Vulnerability type: crlf_injection
  • Vulnerability impact: information_disclosure
  • Requirement type: user_interaction
  • Requirements: Attacker needs the user to click on a malicious link
  • Labels source: projectdiscovery
  • Severity: high
  • Cvss score: 8.8
  • Cvss vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
  • Epss score: 0.01684
  • Epss percentile: 0.77591
  • Assignee: [email protected]
  • Published at: 2018-12-13T16:29:00Z
  • Age in days: 2903
  • Modified at: 2026-06-17T01:40:13Z
  • Patch available: yes
  • References total: 2
  • Products total: 12
  • Advisory url: https://nvd.nist.gov/vuln/detail/CVE-2018-13814
  • Nvd status: modified
  • Checked, none or zero: known exploited entries, nuclei templates, public exploits total, public exploits capped, public exploits, oss, projects total, projects, rejected by nvd
  • Not known: hackerone

Cwe

IdName
CWE-113Improper Neutralization of CRLF Sequences in HTTP Headers
CWE-20Improper Input Validation

References

UrlSourceTags
https://cert-portal.siemens.com/productcert/pdf/ssa-944083.pdfnvdVendor Advisory
http://www.securityfocus.com/bid/105931nvdThird Party Advisory, VDB Entry

Products

Same in every row:

  • Sources: nvd
ProductAffectedPlatform boundUrl
siemens:simatic_wincc_(tia_portal)< 14.0no/v1/products/siemens/simatic_wincc_(tia_portal)
siemens:simatic_wincc_runtime< 14.0no/v1/products/siemens/simatic_wincc_runtime
siemens:simatic_hmi_ktp_mobile_panels_ktp400f_firmware< 14.0yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp400f_firmware
siemens:simatic_hmi_ktp_mobile_panels_ktp700_firmware< 14.0yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp700_firmware
siemens:simatic_hmi_ktp_mobile_panels_ktp700f_firmware< 14.0yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp700f_firmware
siemens:simatic_hmi_ktp_mobile_panels_ktp900_firmware< 14.0yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp900_firmware
siemens:simatic_hmi_ktp_mobile_panels_ktp900f_firmware< 14.0yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp900f_firmware
siemens:simatic_hmi_comfort_panels_firmware< 14.0yes/v1/products/siemens/simatic_hmi_comfort_panels_firmware
siemens:simatic_hmi_comfort_outdoor_panels_firmware< 14.0yes/v1/products/siemens/simatic_hmi_comfort_outdoor_panels_firmware
siemens:simatic_hmi_mp_firmwareall versionsyes/v1/products/siemens/simatic_hmi_mp_firmware

Index

  • Checked, none or zero: repositories, repositories high signal, packages

Exploitation

  • Remote: yes
  • Checked, none or zero: known exploited, known exploited by, exploitation seen, public exploit, public exploit count, initial access, authentication required
  • Not known: known exploited since, vulncheck known exploited since, public exploit first date, nuclei template, initial access since, hackerone reports, exposed hosts