SecurityContext

CVE-2018-4843: Siemens SIMATIC - Denial of Service

  • Cve: CVE-2018-4843
  • Name: Siemens SIMATIC - Denial of Service
  • Description: A vulnerability has been identified in SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V1.7.0), SIMATIC S7-1500 Software Controller (All versions < V1.7.0), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.2.16), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.7), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.1), SIMATIC WinAC RTX 2010 (All versions < V2010 SP3), SIMATIC WinAC RTX F 2010 (All versions < V2010 SP3), SINUMERIK 828D (All versions < V4.7 SP6 HF1), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), Softnet PROFINET IO for PC-based Windows systems (All versions). Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a denial of service condition of the requesting system. The security vulnerability could be exploited by an attacker located on the same Ethernet segment (OSI Layer 2) as the targeted device. A manual restart is required to recover the system.
  • Impact: Attackers can cause denial of service, leading to system unavailability and requiring manual restart to recover.
  • Remediation: Apply latest firmware updates and security patches provided by Siemens for affected devices.
  • Vulnerability type: denial_of_service
  • Vulnerability impact: denial_of_service
  • Requirement type: none
  • Labels source: projectdiscovery
  • Severity: medium
  • Cvss score: 6.5
  • Cvss vector: CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
  • Epss score: 0.00543
  • Epss percentile: 0.46516
  • Assignee: [email protected]
  • Published at: 2018-03-20T14:29:00Z
  • Age in days: 3171
  • Modified at: 2026-06-17T01:59:09Z
  • Patch available: yes
  • References total: 1
  • Products total: 11
  • Advisory url: https://nvd.nist.gov/vuln/detail/CVE-2018-4843
  • Nvd status: modified
  • Checked, none or zero: known exploited entries, nuclei templates, public exploits total, public exploits capped, public exploits, oss, projects total, projects, rejected by nvd
  • Not known: requirements, hackerone

Cwe

IdName
CWE-20Improper Input Validation

References

UrlSourceTags
https://cert-portal.siemens.com/productcert/pdf/ssa-592007.pdfnvdVendor Advisory

Products

Same in every row:

  • Platform bound: yes
  • Sources: nvd
ProductAffectedUrl
siemens:simatic_s7-1500_firmware< 1.7.0/v1/products/siemens/simatic_s7-1500_firmware
siemens:simatic_cp_443-1_firmwareall versions/v1/products/siemens/simatic_cp_443-1_firmware
siemens:simatic_cp_343-1_firmwareall versions/v1/products/siemens/simatic_cp_343-1_firmware
siemens:simatic_s7-300_firmwareall versions/v1/products/siemens/simatic_s7-300_firmware
siemens:simatic_s7-400_pn/dp_v7_firmwareall versions/v1/products/siemens/simatic_s7-400_pn/dp_v7_firmware
siemens:sinumerik_828d_firmwareall versions/v1/products/siemens/sinumerik_828d_firmware
siemens:simatic_s7-410_firmware< 8.1/v1/products/siemens/simatic_s7-410_firmware
siemens:simatic_s7-400_pn/dp_v6_firmware< 6.0.7/v1/products/siemens/simatic_s7-400_pn/dp_v6_firmware
siemens:simatic_s7-400_h_v6_firmwareall versions/v1/products/siemens/simatic_s7-400_h_v6_firmware
siemens:simatic_winac_rtx_2010_firmwareall versions/v1/products/siemens/simatic_winac_rtx_2010_firmware

Index

  • Checked, none or zero: repositories, repositories high signal, packages

Exploitation

  • Checked, none or zero: known exploited, known exploited by, exploitation seen, public exploit, public exploit count, initial access, remote, authentication required
  • Not known: known exploited since, vulncheck known exploited since, public exploit first date, nuclei template, initial access since, hackerone reports, exposed hosts