CVE-2019-10918: Siemens SIMATIC PCS 7 & WinCC - Command Injection
- Cve: CVE-2019-10918
- Name: Siemens SIMATIC PCS 7 & WinCC - Command Injection
- Description: A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
- Impact: Attackers can execute arbitrary commands with SYSTEM privileges, compromising confidentiality, integrity, and availability of the affected system.
- Remediation: Apply the latest security updates and patches provided by Siemens for affected versions.
- Vulnerability type: command_injection
- Vulnerability impact: remote_code_execution, privilege_escalation
- Requirement type: logged_in
- Requirements: Attacker needs to authenticate with a low-privileged user account
- Labels source: projectdiscovery
- Severity: high
- Cvss score: 8.8
- Cvss vector: CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
- Epss score: 0.01926
- Epss percentile: 0.80492
- Assignee: [email protected]
- Published at: 2019-05-14T20:29:02Z
- Age in days: 2751
- Modified at: 2026-06-17T02:11:54Z
- References total: 2
- Products total: 4
- Advisory url: https://nvd.nist.gov/vuln/detail/CVE-2019-10918
- Nvd status: modified
- Checked, none or zero: patch available, known exploited entries, nuclei templates, public exploits total, public exploits capped, public exploits, oss, projects total, projects, rejected by nvd
- Not known: hackerone
Cwe
| Id | Name |
|---|---|
| CWE-749 | Exposed Dangerous Method or Function |
| NVD-CWE-Other | — |
References
| Url | Source | Tags |
|---|---|---|
| https://cert-portal.siemens.com/productcert/pdf/ssa-697412.pdf | nvd | Vendor Advisory |
| https://www.us-cert.gov/ics/advisories/ICSA-19-134-08 | nvd | Third Party Advisory, US Government Resource |
Products
Same in every row:
- Platform bound: no
- Sources: nvd
| Product | Affected | Url |
|---|---|---|
| siemens:simatic_wincc | = 7.5, = 7.4, = 7.3, <= 7.2 | /v1/products/siemens/simatic_wincc |
| siemens:simatic_pcs_7 | = 9.0, = 8.2, = 8.1, <= 8.0 | /v1/products/siemens/simatic_pcs_7 |
| siemens:simatic_wincc_(tia_portal) | = 15.0, = 14.0, = 13.0 | /v1/products/siemens/simatic_wincc_(tia_portal) |
| siemens:simatic_wincc_runtime_professional | all versions | /v1/products/siemens/simatic_wincc_runtime_professional |
Index
- Checked, none or zero: repositories, repositories high signal, packages
Exploitation
- Remote: yes
- Authentication required: yes
- Checked, none or zero: known exploited, known exploited by, exploitation seen, public exploit, public exploit count, initial access
- Not known: known exploited since, vulncheck known exploited since, public exploit first date, nuclei template, initial access since, hackerone reports, exposed hosts