SecurityContext

CVE-2019-10938: Siemens SIPROTEC & Power Meters - Remote Code Execution

  • Cve: CVE-2019-10938
  • Name: Siemens SIPROTEC & Power Meters - Remote Code Execution
  • Description: A vulnerability has been identified in SIPROTEC 5 devices with CPU variants CP200 (All versions < V7.59), SIPROTEC 5 devices with CPU variants CP300 and CP100 (All versions < V8.01), Siemens Power Meters Series 9410 (All versions < V2.2.1), Siemens Power Meters Series 9810 (All versions). An unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
  • Impact: Attackers can execute arbitrary code on the device, potentially leading to device control or disruption of operations.
  • Remediation: Update to the latest firmware versions: SIPROTEC 5 V7.59 or later, Power Meters Series 9410 V2.2.1 or later, Series 9810 latest version.
  • Vulnerability type: insecure_deserialization
  • Vulnerability impact: remote_code_execution
  • Requirement type: none
  • Labels source: projectdiscovery
  • Severity: critical
  • Cvss score: 9.8
  • Cvss vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
  • Epss score: 0.01495
  • Epss percentile: 0.74839
  • Assignee: [email protected]
  • Published at: 2019-08-02T14:15:14Z
  • Age in days: 2671
  • Modified at: 2026-06-17T02:11:57Z
  • Patch available: yes
  • References total: 2
  • Products total: 1
  • Advisory url: https://nvd.nist.gov/vuln/detail/CVE-2019-10938
  • Nvd status: modified
  • Checked, none or zero: known exploited entries, nuclei templates, public exploits total, public exploits capped, public exploits, oss, projects total, projects, rejected by nvd
  • Not known: requirements, hackerone

Cwe

IdName
CWE-284Improper Access Control
NVD-CWE-Other—

References

UrlSourceTags
https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdfnvdMitigation, Patch, Vendor Advisory
https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdfnvdMitigation, Patch, Vendor Advisory

Products

ProductAffectedPlatform boundSourcesUrl
siemens:siprotec_5_digsi_device_driverall versionsyesnvd/v1/products/siemens/siprotec_5_digsi_device_driver

Index

  • Checked, none or zero: repositories, repositories high signal, packages

Exploitation

  • Remote: yes
  • Checked, none or zero: known exploited, known exploited by, exploitation seen, public exploit, public exploit count, initial access, authentication required
  • Not known: known exploited since, vulncheck known exploited since, public exploit first date, nuclei template, initial access since, hackerone reports, exposed hosts