CVE-2019-6575: Siemens SIMATIC - Denial of Service

  • Cve: CVE-2019-6575
  • Name: Siemens SIMATIC - Denial of Service
  • Description: A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions < V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions < V1.1.0), SIMATIC RF600R family (All versions < V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 < V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions < V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Upd 4), SINEC NMS (All versions < V1.0 SP1), SINEMA Server (All versions < V14 SP2), SINUMERIK OPC UA Server (All versions < V2.1), TeleControl Server Basic (All versions < V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication.
  • Impact: Attackers can cause device crashes or communication denial, disrupting industrial operations and affecting system availability.
  • Remediation: Update affected devices and software to the latest versions provided by Siemens that address this vulnerability.
  • Vulnerability type: denial_of_service
  • Vulnerability impact: denial_of_service
  • Requirement type: none
  • Labels source: projectdiscovery
  • Severity: high
  • Cvss score: 7.5
  • Cvss vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
  • Epss score: 0.01678
  • Epss percentile: 0.77514
  • Assignee: [email protected]
  • Published at: 2019-04-17T14:29:03Z
  • Age in days: 2778
  • Modified at: 2026-06-17T02:39:17Z
  • Patch available: yes
  • References total: 1
  • Products total: 27
  • Advisory url: https://nvd.nist.gov/vuln/detail/CVE-2019-6575
  • Nvd status: modified
  • Checked, none or zero: known exploited entries, nuclei templates, public exploits total, public exploits capped, public exploits, oss, projects total, projects, rejected by nvd
  • Not known: requirements, hackerone

Cwe

IdName
CWE-248Uncaught Exception
CWE-755Improper Handling of Exceptional Conditions

References

UrlSourceTags
https://cert-portal.siemens.com/productcert/pdf/ssa-307392.pdfnvdVendor Advisory

Products

Same in every row:

  • Sources: nvd
ProductAffectedPlatform boundUrl
siemens:telecontrol_server_basic< 3.1.1no/v1/products/siemens/telecontrol_server_basic
siemens:sinema_serverall versionsno/v1/products/siemens/sinema_server
siemens:simatic_wincc_runtime_advancedall versionsno/v1/products/siemens/simatic_wincc_runtime_advanced
siemens:simatic_s7-1500_software_controller<= 2.5no/v1/products/siemens/simatic_s7-1500_software_controller
siemens:simatic_wincc_oa< 3.15-p018no/v1/products/siemens/simatic_wincc_oa
siemens:sinumerik_opc_ua_server< 2.1no/v1/products/siemens/sinumerik_opc_ua_server
siemens:simatic_hmi_ktp_mobile_panels_ktp400f_firmware< 15.1, = 15.1, = 15.1 upd_1, = 15.1 upd_2, = 15.1 upd_3yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp400f_firmware
siemens:simatic_hmi_ktp_mobile_panels_ktp700_firmware< 15.1, = 15.1, = 15.1 upd_1, = 15.1 upd_2, = 15.1 upd_3yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp700_firmware
siemens:simatic_hmi_ktp_mobile_panels_ktp700f_firmware< 15.1, = 15.1, = 15.1 upd_1, = 15.1 upd_2, = 15.1 upd_3yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp700f_firmware
siemens:simatic_hmi_ktp_mobile_panels_ktp900_firmware< 15.1, = 15.1, = 15.1 upd_1, = 15.1 upd_2, = 15.1 upd_3yes/v1/products/siemens/simatic_hmi_ktp_mobile_panels_ktp900_firmware