SecurityContext

CVE-2022-33175: Power Distribution Units - Broken Access Control

  • Cve: CVE-2022-33175
  • Name: Power Distribution Units - Broken Access Control
  • Description: Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.
  • Impact: Attackers can hijack administrator sessions, potentially leading to device reconfiguration, password disclosure, and full control over the PDU.
  • Remediation: Update firmware to version 3.30.30 or later to fix permission issues on user.token.
  • Vulnerability type: broken_access_control
  • Vulnerability impact: information_disclosure, privilege_escalation, data_tampering
  • Requirement type: none
  • Labels source: projectdiscovery
  • Severity: critical
  • Cvss score: 9.8
  • Cvss vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
  • Epss score: 0.01738
  • Epss percentile: 0.78307
  • Assignee: [email protected]
  • Published at: 2022-06-13T18:15:10Z
  • Age in days: 1625
  • Modified at: 2026-06-17T04:48:32Z
  • Patch available: yes
  • Public exploits total: 1
  • References total: 1
  • Products total: 7
  • Advisory url: https://nvd.nist.gov/vuln/detail/CVE-2022-33175
  • Nvd status: modified
  • Checked, none or zero: known exploited entries, nuclei templates, public exploits capped, oss, projects total, projects, rejected by nvd
  • Not known: requirements, hackerone

Cwe

IdName
CWE-732Incorrect Permission Assignment for Critical Resource

Public exploits

UrlSourceAdded date
https://gynvael.coldwind.pl/?lang=en&id=748nvd2022-06-13

References

UrlSourceTags
https://gynvael.coldwind.pl/?lang=en&id=748nvdExploit, Third Party Advisory

Products

Same in every row:

  • Affected: < 3.30.30
  • Platform bound: yes
  • Sources: nvd
ProductUrl
powertekpdus:basic_pdu_firmware/v1/products/powertekpdus/basic_pdu_firmware
powertekpdus:piml_pdu_firmware/v1/products/powertekpdus/piml_pdu_firmware
powertekpdus:pm_pdu_firmware/v1/products/powertekpdus/pm_pdu_firmware
powertekpdus:smart_pim_firmware/v1/products/powertekpdus/smart_pim_firmware
powertekpdus:smart_pom_firmware/v1/products/powertekpdus/smart_pom_firmware
powertekpdus:smart_poms_firmware/v1/products/powertekpdus/smart_poms_firmware
powertekpdus:smart_pos_firmware/v1/products/powertekpdus/smart_pos_firmware

Index

  • Checked, none or zero: repositories, repositories high signal, packages

Exploitation

  • Public exploit: yes
  • Public exploit count: 1
  • Public exploit first date: 2022-06-13
  • Remote: yes
  • Exposed hosts: 7
  • Checked, none or zero: known exploited, known exploited by, exploitation seen, initial access, authentication required
  • Not known: known exploited since, vulncheck known exploited since, nuclei template, initial access since, hackerone reports